This paper describes some critical issues arising during the partial discharge (PD) testing of a 500m delivery length of an XLPE-insulated MV cable. At first, conventional PD measurements were performed on the whole length by using a standard acquisition system; PDs activity was detected, but the system allowed the operator to localize the PDs only on a length of 70 m. A visual inspection of this section highlighted the presence of an excoriation in the outer sheet. Aiming at a more accurate pin-pointing of the defect, more measurements were carried out in the proximity of the outer defect using a portable PD detection system. These measurements showed PDs activity, whose source was located and identified as consisting in internal defects on the inner semicon in proximity of the external excoriation. This proves how PD detection portable instruments are able, in cases like this, to locate the PD source and provide indications for its correct classification.

Madonia, A., Riva Sanseverino, E., Troia, I., Franchi Bononi, S., Giannini, S., Mazzanti, G. (2018). Critical issues in the PD testing methodology for XLPE-insulated MV cables: an experimental case. In Proceedings of IEEE Conference on Electrical Insulation and Dielectric Phenomenon (CEIDP) (pp. 311-314) [10.1109/CEIDP.2017.8257449].

Critical issues in the PD testing methodology for XLPE-insulated MV cables: an experimental case

Riva Sanseverino, Eleonora;
2018-01-15

Abstract

This paper describes some critical issues arising during the partial discharge (PD) testing of a 500m delivery length of an XLPE-insulated MV cable. At first, conventional PD measurements were performed on the whole length by using a standard acquisition system; PDs activity was detected, but the system allowed the operator to localize the PDs only on a length of 70 m. A visual inspection of this section highlighted the presence of an excoriation in the outer sheet. Aiming at a more accurate pin-pointing of the defect, more measurements were carried out in the proximity of the outer defect using a portable PD detection system. These measurements showed PDs activity, whose source was located and identified as consisting in internal defects on the inner semicon in proximity of the external excoriation. This proves how PD detection portable instruments are able, in cases like this, to locate the PD source and provide indications for its correct classification.
15-gen-2018
978-1-5386-1194-4
Madonia, A., Riva Sanseverino, E., Troia, I., Franchi Bononi, S., Giannini, S., Mazzanti, G. (2018). Critical issues in the PD testing methodology for XLPE-insulated MV cables: an experimental case. In Proceedings of IEEE Conference on Electrical Insulation and Dielectric Phenomenon (CEIDP) (pp. 311-314) [10.1109/CEIDP.2017.8257449].
File in questo prodotto:
File Dimensione Formato  
Critical_issues_in_the_PD_testing_methodology_for_XLPE-insulated_MV_cables_An_experimental_case.pdf

Solo gestori archvio

Tipologia: Versione Editoriale
Dimensione 1.43 MB
Formato Adobe PDF
1.43 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/667097
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 5
  • ???jsp.display-item.citation.isi??? ND
social impact