Variable-speed packaged rooftop units have been increasingly adopted in the commercial sector. If not properly maintained, the fouling of heat exchangers and the improper refrigerant charge could increase energy consumption. In this work, the response of variable-speed rooftop units to evaporator fouling is investigated based on experiments on a variable-speed 17.5 kW rooftop unit. A novel testing procedure is proposed, aimed at covering a broad range of operating conditions by a reduced number of tests. Two opposite cases were investigated: (i) even in presence of fouling, the controller can restore the required cooling capacity, and (ii) the intensity of the fouling does not allow the controller to restore the cooling capacity. While in the former case an increase in the indoor fan rotating speed is observed, with no variations in the evaporating pressure and the inlet temperature of cooled air, in the latter one the mismatch between the cooling load and the capacity induces a deviation of the indoor air condition from the setpoint. A regression model is proposed to quantify these deviations. Experimental results showed that in a faulty scenario, the maximum cooling capacity deliverable could decrease up to 15-20 %, and the indoor fan consumption increased up to 40%. In case of heavy faults involving cooling capacity shortage, a 2.3 °C deviation from the indoor setpoint temperature was estimated by the proposed regression model.

Catrini P, Piacentino A (2022). Experimental characterization of variable-speed packaged rooftop units in presence of evaporator fouling. In Proceedings of 17th Conference on Sustainable Development of Energy, Water and Environment Systems (pp. 1-18). Paphos.

Experimental characterization of variable-speed packaged rooftop units in presence of evaporator fouling

Catrini P
;
Piacentino A
2022-11-01

Abstract

Variable-speed packaged rooftop units have been increasingly adopted in the commercial sector. If not properly maintained, the fouling of heat exchangers and the improper refrigerant charge could increase energy consumption. In this work, the response of variable-speed rooftop units to evaporator fouling is investigated based on experiments on a variable-speed 17.5 kW rooftop unit. A novel testing procedure is proposed, aimed at covering a broad range of operating conditions by a reduced number of tests. Two opposite cases were investigated: (i) even in presence of fouling, the controller can restore the required cooling capacity, and (ii) the intensity of the fouling does not allow the controller to restore the cooling capacity. While in the former case an increase in the indoor fan rotating speed is observed, with no variations in the evaporating pressure and the inlet temperature of cooled air, in the latter one the mismatch between the cooling load and the capacity induces a deviation of the indoor air condition from the setpoint. A regression model is proposed to quantify these deviations. Experimental results showed that in a faulty scenario, the maximum cooling capacity deliverable could decrease up to 15-20 %, and the indoor fan consumption increased up to 40%. In case of heavy faults involving cooling capacity shortage, a 2.3 °C deviation from the indoor setpoint temperature was estimated by the proposed regression model.
nov-2022
Settore ING-IND/10 - Fisica Tecnica Industriale
Catrini P, Piacentino A (2022). Experimental characterization of variable-speed packaged rooftop units in presence of evaporator fouling. In Proceedings of 17th Conference on Sustainable Development of Energy, Water and Environment Systems (pp. 1-18). Paphos.
File in questo prodotto:
File Dimensione Formato  
Fouling - Catrini and Piacentino.pdf

Solo gestori archvio

Tipologia: Pre-print
Dimensione 532.68 kB
Formato Adobe PDF
532.68 kB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/583012
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
social impact