In the last years different partial discharge (PD) measuring techniques have been developed because PD diagnostic is the most widely tool to evaluate the insulation condition of a power cable. Recently non-conventional methods and sensors have been used in order to reach improved results in PD measurements. New sensors based on wireless technology were developed in order to simplify PD measurement especially for on-line, on-site diagnosis. The purpose of this work is to perform measurements that allow to study the variation of pulses when they travel along a medium voltage cable and characterize a new smart PD source detector and locator, named Wings sensor. For these purposes, internal PD signals have been acquired and compared with those detected by the dassical PD acquisition system. In addition, the characterization of the Wings sensor has been completed by acquiring PD pulses when the sensor is placed at different rotation angle and distance from the cable. It was found that for a better voltage magnitude signal the sensor should be placed in parallel with the cable and in contact with it.

Romano, P., Imburgia, A., De Rai, L. (2018). Partial Discharges Diagnostics Along Medium Voltage Cables. In IEEE 4th International Forum on Research and Technologies for Society and Industry, RTSI 2018 - Proceedings (pp. 1-4). Institute of Electrical and Electronics Engineers Inc. [10.1109/RTSI.2018.8548443].

Partial Discharges Diagnostics Along Medium Voltage Cables

Romano, P.;Imburgia, A.;
2018-01-01

Abstract

In the last years different partial discharge (PD) measuring techniques have been developed because PD diagnostic is the most widely tool to evaluate the insulation condition of a power cable. Recently non-conventional methods and sensors have been used in order to reach improved results in PD measurements. New sensors based on wireless technology were developed in order to simplify PD measurement especially for on-line, on-site diagnosis. The purpose of this work is to perform measurements that allow to study the variation of pulses when they travel along a medium voltage cable and characterize a new smart PD source detector and locator, named Wings sensor. For these purposes, internal PD signals have been acquired and compared with those detected by the dassical PD acquisition system. In addition, the characterization of the Wings sensor has been completed by acquiring PD pulses when the sensor is placed at different rotation angle and distance from the cable. It was found that for a better voltage magnitude signal the sensor should be placed in parallel with the cable and in contact with it.
2018
Settore ING-IND/31 - Elettrotecnica
9781538662823
Romano, P., Imburgia, A., De Rai, L. (2018). Partial Discharges Diagnostics Along Medium Voltage Cables. In IEEE 4th International Forum on Research and Technologies for Society and Industry, RTSI 2018 - Proceedings (pp. 1-4). Institute of Electrical and Electronics Engineers Inc. [10.1109/RTSI.2018.8548443].
File in questo prodotto:
File Dimensione Formato  
Partial Discharges Diagnostics Along Medium Voltage Cables.pdf

Solo gestori archvio

Descrizione: paper
Tipologia: Versione Editoriale
Dimensione 485.99 kB
Formato Adobe PDF
485.99 kB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/347830
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 2
  • ???jsp.display-item.citation.isi??? ND
social impact