This paper summarizes the authors research activity concerning the design, modeling and experimental characterization of a new coupling system for medium voltage (MV) narrow band power line communications (NB-PLC). The proposed solution has been patented by authors and it exploits the capacitive divider of voltage detecting systems (VDSs) normally used to reveal the mains voltage presence, thus avoiding the use of dedicated MV couplers. In the following, the modeling of the VDS capacitive divider is presented and the interface card design is described, based on simulation of the whole PLC transmission channel. Laboratory tests are also presented. Finally, the results are shown of an on-field measurement campaign, which has been carried out the MV distribution networks of the Islands of Ustica and Favignana. Transmission tests demonstrate that the proposed VDS coupling system can be effective for narrowband modulated signal transmission.

Giovanni Artale, A.C. (2018). An innovative power line communication solution for medium voltage smart grids applications. In Atti del II FORUM NAZIONALE DELLE MISURE (pp. 65-74).

An innovative power line communication solution for medium voltage smart grids applications

Giovanni Artale;Antonio Cataliotti;Valentina Cosentino;Salvatore Guaiana;Nicola Panzavecchia;
2018-01-01

Abstract

This paper summarizes the authors research activity concerning the design, modeling and experimental characterization of a new coupling system for medium voltage (MV) narrow band power line communications (NB-PLC). The proposed solution has been patented by authors and it exploits the capacitive divider of voltage detecting systems (VDSs) normally used to reveal the mains voltage presence, thus avoiding the use of dedicated MV couplers. In the following, the modeling of the VDS capacitive divider is presented and the interface card design is described, based on simulation of the whole PLC transmission channel. Laboratory tests are also presented. Finally, the results are shown of an on-field measurement campaign, which has been carried out the MV distribution networks of the Islands of Ustica and Favignana. Transmission tests demonstrate that the proposed VDS coupling system can be effective for narrowband modulated signal transmission.
2018
978-88-31901-06-2
Giovanni Artale, A.C. (2018). An innovative power line communication solution for medium voltage smart grids applications. In Atti del II FORUM NAZIONALE DELLE MISURE (pp. 65-74).
File in questo prodotto:
File Dimensione Formato  
GMEE 2018_An innovative power line communication solution.pdf

Solo gestori archvio

Descrizione: Articolo
Tipologia: Versione Editoriale
Dimensione 6.11 MB
Formato Adobe PDF
6.11 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/339960
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
social impact