International Standards define a Global Earthing System as an earthing net created interconnecting local Earthing Systems (generally through the shield of MV cables and/or bare buried conductors). In Italy the Regulatory Authority for Electricity and Gas requires Distributors to guarantee the electrical continuity of LV neutral conductor. This requirement has led to the standard practice of realizing 'reinforcement groundings' along the LV neutral conductor path and at users' delivery cabinet. Moreover, in urban high load scenarios (prime candidates to be part of a Global Earthing System), it is common that LV distribution scheme creates, through neutral conductors, an effective connection between grounding systems of MV/LV substations, modifying Global Earthing System consistency. Aim of this paper is to evaluate the effect, in terms of electrical safety, of the above mentioned LV neutral distribution scheme when an MV-side fault to ground occurs. At this purpose simulations are carried out on a realistic urban test case and suitable evaluation indexes are proposed.

Cafaro, G., Montegiglio, P., Torelli, F., Barresi, A., Colella, P., De Simone, A., et al. (2015). Influence of LV neutral grounding on global Earthing Systems. In 2015 IEEE 15th International Conference on Environment and Electrical Engineering, EEEIC 2015 - Conference Proceedings (pp.389-394). Institute of Electrical and Electronics Engineers Inc. [10.1109/EEEIC.2015.7165193].

Influence of LV neutral grounding on global Earthing Systems

DI SILVESTRE, Maria Luisa;RIVA SANSEVERINO, Eleonora;ZIZZO, Gaetano
2015-01-01

Abstract

International Standards define a Global Earthing System as an earthing net created interconnecting local Earthing Systems (generally through the shield of MV cables and/or bare buried conductors). In Italy the Regulatory Authority for Electricity and Gas requires Distributors to guarantee the electrical continuity of LV neutral conductor. This requirement has led to the standard practice of realizing 'reinforcement groundings' along the LV neutral conductor path and at users' delivery cabinet. Moreover, in urban high load scenarios (prime candidates to be part of a Global Earthing System), it is common that LV distribution scheme creates, through neutral conductors, an effective connection between grounding systems of MV/LV substations, modifying Global Earthing System consistency. Aim of this paper is to evaluate the effect, in terms of electrical safety, of the above mentioned LV neutral distribution scheme when an MV-side fault to ground occurs. At this purpose simulations are carried out on a realistic urban test case and suitable evaluation indexes are proposed.
Settore ING-IND/33 - Sistemi Elettrici Per L'Energia
Settore ING-IND/31 - Elettrotecnica
15th IEEE International Conference on Environment and Electrical Engineering, EEEIC 2015
Rome, Italy
10-13 June 2015
2015
6
https://ieeexplore.ieee.org/document/7165193
Cafaro, G., Montegiglio, P., Torelli, F., Barresi, A., Colella, P., De Simone, A., et al. (2015). Influence of LV neutral grounding on global Earthing Systems. In 2015 IEEE 15th International Conference on Environment and Electrical Engineering, EEEIC 2015 - Conference Proceedings (pp.389-394). Institute of Electrical and Electronics Engineers Inc. [10.1109/EEEIC.2015.7165193].
Proceedings (atti dei congressi)
Cafaro, G.; Montegiglio, P.; Torelli, F.; Barresi, A.; Colella, P.; De Simone, A.; Di Silvestre, M.; Martirano, L.; Morozova, E.; Napoli, R.; Parise, G.; Parise, L.; Pons, E.; Riva Sanseverino, E.; Tommasini, R.; Tummolillo, F.; Valtorta, G.; Zizzo, G.
File in questo prodotto:
File Dimensione Formato  
EEEIC_Influence of LV neutral grounding on global Earthing Systems.pdf

Solo gestori archvio

Dimensione 891.49 kB
Formato Adobe PDF
891.49 kB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/176355
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 11
  • ???jsp.display-item.citation.isi??? 9
social impact