When a single line to ground fault happens on the MV side of a HV/MV system, only a small portion of the fault current is injected into the ground by the ground-grid of the faulty substation. In fact the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real single line to ground fault was made and fault currents were measured in the faulty substation and in four neighboring substations. In this paper the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.

Colella, P., Napoli, R., Pons, E., Tommasini, R., Barresi, A., Cafaro, G., et al. (2016). Currents distribution during a fault in a MV Network: Methods and measurements. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 52 (6), 4585-4593 [10.1109/TIA.2016.2600672].

Currents distribution during a fault in a MV Network: Methods and measurements

DI SILVESTRE, Maria Luisa;RIVA SANSEVERINO, Eleonora;ZIZZO, Gaetano
2016-01-01

Abstract

When a single line to ground fault happens on the MV side of a HV/MV system, only a small portion of the fault current is injected into the ground by the ground-grid of the faulty substation. In fact the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real single line to ground fault was made and fault currents were measured in the faulty substation and in four neighboring substations. In this paper the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.
2016
Colella, P., Napoli, R., Pons, E., Tommasini, R., Barresi, A., Cafaro, G., et al. (2016). Currents distribution during a fault in a MV Network: Methods and measurements. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 52 (6), 4585-4593 [10.1109/TIA.2016.2600672].
File in questo prodotto:
File Dimensione Formato  
IEEETIA_2016_Currents distribution during a faultin an MV Network_Methods and measurements.pdf

Solo gestori archvio

Dimensione 1.11 MB
Formato Adobe PDF
1.11 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/224004
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 19
  • ???jsp.display-item.citation.isi??? 18
social impact