When a single line to ground fault happens on the MV side of a HV/MV system, only a small portion of the fault current is injected into the ground by the ground-grid of the faulty substation. In fact the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real single line to ground fault was made and fault currents were measured in the faulty substation and in four neighboring substations. In this paper the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.
Colella, P., Napoli, R., Pons, E., Tommasini, R., Barresi, A., Cafaro, G., et al. (2016). Currents distribution during a fault in a MV Network: Methods and measurements. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 52 (6), 4585-4593 [10.1109/TIA.2016.2600672].
Currents distribution during a fault in a MV Network: Methods and measurements
DI SILVESTRE, Maria Luisa;RIVA SANSEVERINO, Eleonora;ZIZZO, Gaetano
2016-01-01
Abstract
When a single line to ground fault happens on the MV side of a HV/MV system, only a small portion of the fault current is injected into the ground by the ground-grid of the faulty substation. In fact the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real single line to ground fault was made and fault currents were measured in the faulty substation and in four neighboring substations. In this paper the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.File | Dimensione | Formato | |
---|---|---|---|
IEEETIA_2016_Currents distribution during a faultin an MV Network_Methods and measurements.pdf
Solo gestori archvio
Dimensione
1.11 MB
Formato
Adobe PDF
|
1.11 MB | Adobe PDF | Visualizza/Apri Richiedi una copia |
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.