When a substation is fed by a combined overheadcable transmission line, a significant part of the ground fault current flows through the grounded cable sheaths and discharges into the earth at the transition station, where cables are connected to the overhead line. If the transition station is a dead-end steel pole structure, the local ground electrode, small and of high resistance, could be inadequate to maintain the ground potential rise within safety limits in case of a fault to ground at the receiving end substation. Based on a circuit model approach, the paper presents a parametric analysis of the fault current distribution between the faulted substation and the transition station, taking into account of all the relevant parameters.

MANGIONE S (2007). Ground-Fault Current Transfer at the Transition Station of a Combined Overhead-Cable Line. A Parametric Analysis. In 2007 International Conference on Power Engineering, Energy and Electrical Drives (pp.394-399) [10.1109/POWERENG.2007.4380136].

Ground-Fault Current Transfer at the Transition Station of a Combined Overhead-Cable Line. A Parametric Analysis

MANGIONE, Stefano
2007-01-01

Abstract

When a substation is fed by a combined overheadcable transmission line, a significant part of the ground fault current flows through the grounded cable sheaths and discharges into the earth at the transition station, where cables are connected to the overhead line. If the transition station is a dead-end steel pole structure, the local ground electrode, small and of high resistance, could be inadequate to maintain the ground potential rise within safety limits in case of a fault to ground at the receiving end substation. Based on a circuit model approach, the paper presents a parametric analysis of the fault current distribution between the faulted substation and the transition station, taking into account of all the relevant parameters.
Settore ING-IND/33 - Sistemi Elettrici Per L'Energia
POWERENG International Conference on Power Engineering, Energy and Electrical Drives
Setùbal (Portugal)
12-14 April 2007
2007
6
IEEE Catalog Number 07EX1654C
MANGIONE S (2007). Ground-Fault Current Transfer at the Transition Station of a Combined Overhead-Cable Line. A Parametric Analysis. In 2007 International Conference on Power Engineering, Energy and Electrical Drives (pp.394-399) [10.1109/POWERENG.2007.4380136].
Proceedings (atti dei congressi)
MANGIONE S
File in questo prodotto:
File Dimensione Formato  
Ground-Fault.pdf

Solo gestori archvio

Dimensione 5.95 MB
Formato Adobe PDF
5.95 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/25238
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 4
  • ???jsp.display-item.citation.isi??? 1
social impact