The paper presents an analysis methodology for a single-line-to-ground fault, occurring at a secondary MV/LV substation in a power network formed by a HV7MV station, feeding, through a MV tri-phase cable line, N MV/LV substations whose earth electrodes are interconnected by bare buried conductors. Preliminary explayning the methodology, earth buried conductors are studied in their double function of earth electrodes and connection elements between earthing grids, both in absence and in presence of other interfering conductors. Subsequently is analyzed, with a distributed parameters approach, the system constituted by an earth buried conductor and a MV tri-phase cable line. The equations that describe system behaviour are solved with the decoupling method of Modal Analysis. The proposed methodology allows to determinate the currents injected in the ground by the buried conductor and by the earth electrodes of the substations, as a consequence of an earth fault, whichever is the faulty substation. A numerical example clarifies the presented methodology. © 2003 IEEE.

Campoccia, A., Di Silvestre, M., Zizzo, G. (2003). An analysis methodology to evaluate the contribution to electrical security given by bare buried conductors in a system of intertied earthing grids. In 2003 IEEE Bologna PowerTech - Conference Proceedings (pp.1012-1019) [10.1109/PTC.2003.1304515].

An analysis methodology to evaluate the contribution to electrical security given by bare buried conductors in a system of intertied earthing grids

CAMPOCCIA, Angelo;DI SILVESTRE, Maria Luisa;ZIZZO, Gaetano
2003-01-01

Abstract

The paper presents an analysis methodology for a single-line-to-ground fault, occurring at a secondary MV/LV substation in a power network formed by a HV7MV station, feeding, through a MV tri-phase cable line, N MV/LV substations whose earth electrodes are interconnected by bare buried conductors. Preliminary explayning the methodology, earth buried conductors are studied in their double function of earth electrodes and connection elements between earthing grids, both in absence and in presence of other interfering conductors. Subsequently is analyzed, with a distributed parameters approach, the system constituted by an earth buried conductor and a MV tri-phase cable line. The equations that describe system behaviour are solved with the decoupling method of Modal Analysis. The proposed methodology allows to determinate the currents injected in the ground by the buried conductor and by the earth electrodes of the substations, as a consequence of an earth fault, whichever is the faulty substation. A numerical example clarifies the presented methodology. © 2003 IEEE.
2003 IEEE Bologna PowerTech Conference
Bologna, ita
2003
2003
8
Campoccia, A., Di Silvestre, M., Zizzo, G. (2003). An analysis methodology to evaluate the contribution to electrical security given by bare buried conductors in a system of intertied earthing grids. In 2003 IEEE Bologna PowerTech - Conference Proceedings (pp.1012-1019) [10.1109/PTC.2003.1304515].
Proceedings (atti dei congressi)
Campoccia, A.; Di Silvestre, M.; Zizzo, G.
File in questo prodotto:
File Dimensione Formato  
Powertech_2003.pdf

Solo gestori archvio

Descrizione: articolo principale
Dimensione 544.54 kB
Formato Adobe PDF
544.54 kB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/230650
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 7
  • ???jsp.display-item.citation.isi??? ND
social impact