Medium Voltage collector cables of Wind Farms have metal shields connected to the grounding systems of the towers and of the connection station. Thanks to this bonding, when a ground fault occurs, the fault current splits itself among all the grounding systems of the wind farm, this causing a reduction of the ground potential rise at the fault location. Nevertheless, in presence of double ground faults, very high ground potential rises occur at the two fault locations and safety against electric shock is not always assured. In order to study this issue, the paper presents a model for simulating in a simple way the effects of double ground faults occurring in Medium Voltage collectors of extended wind plants connected to the High Voltage network.

LA CASCIA, D., Zizzo, G. (2015). Effects of double ground faults in Wind Farms collector cables. In 2015 IEEE 15th International Conference on Environment and Electrical Engineering (EEEIC) (pp.66-70). Institute of Electrical and Electronics Engineers Inc. [10.1109/EEEIC.2015.7165351].

Effects of double ground faults in Wind Farms collector cables

LA CASCIA, Diego;ZIZZO, Gaetano
2015-01-01

Abstract

Medium Voltage collector cables of Wind Farms have metal shields connected to the grounding systems of the towers and of the connection station. Thanks to this bonding, when a ground fault occurs, the fault current splits itself among all the grounding systems of the wind farm, this causing a reduction of the ground potential rise at the fault location. Nevertheless, in presence of double ground faults, very high ground potential rises occur at the two fault locations and safety against electric shock is not always assured. In order to study this issue, the paper presents a model for simulating in a simple way the effects of double ground faults occurring in Medium Voltage collectors of extended wind plants connected to the High Voltage network.
Settore ING-IND/33 - Sistemi Elettrici Per L'Energia
giu-2015
15th IEEE International Conference on Environment and Electrical Engineering, EEEIC 2015
ita
2015
2015
5
https://ieeexplore.ieee.org/document/7165351
LA CASCIA, D., Zizzo, G. (2015). Effects of double ground faults in Wind Farms collector cables. In 2015 IEEE 15th International Conference on Environment and Electrical Engineering (EEEIC) (pp.66-70). Institute of Electrical and Electronics Engineers Inc. [10.1109/EEEIC.2015.7165351].
Proceedings (atti dei congressi)
LA CASCIA, D.; Zizzo, G.
File in questo prodotto:
File Dimensione Formato  
2015_EEEEIC_035.pdf

Solo gestori archvio

Dimensione 197.73 kB
Formato Adobe PDF
197.73 kB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/204038
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 2
  • ???jsp.display-item.citation.isi??? 0
social impact