The paper proposes three simple circuit models for the simulation of the behaviour of a global earthing system during different fault events. The models allow one the evaluation of the maximum earth potential rise at every possible fault location and for every possible fault event. The three considered fault events are: single-line-to-earth fault inside a MV/LV substation, double-earth-fault in a MV line, single-line-to-earth fault inside a HV/MV station. After having illustrated the hypotheses at the basis of the study, the circuit models for the three fault events are presented and a numerical example shows how to use them in order to check the "global safety" of the interconnected earthing systems.
A CAMPOCCIA, ZIZZO G (2007). Simple Circuit Models for Studying Global Earthing Systems. In Proceedings of IEEE Powertech 2007 (pp.1947-1952) [10.1109/PCT.2007.4538615].
Simple Circuit Models for Studying Global Earthing Systems
CAMPOCCIA, Angelo;ZIZZO, Gaetano
2007-01-01
Abstract
The paper proposes three simple circuit models for the simulation of the behaviour of a global earthing system during different fault events. The models allow one the evaluation of the maximum earth potential rise at every possible fault location and for every possible fault event. The three considered fault events are: single-line-to-earth fault inside a MV/LV substation, double-earth-fault in a MV line, single-line-to-earth fault inside a HV/MV station. After having illustrated the hypotheses at the basis of the study, the circuit models for the three fault events are presented and a numerical example shows how to use them in order to check the "global safety" of the interconnected earthing systems.File | Dimensione | Formato | |
---|---|---|---|
Simple Circuit Models.pdf
Solo gestori archvio
Dimensione
377.75 kB
Formato
Adobe PDF
|
377.75 kB | Adobe PDF | Visualizza/Apri Richiedi una copia |
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.