A Global Grounding System is defined as the combination of local grounding systems, obtained by their interconnection, which ensures, thanks to their proximity, that no dangerous touch voltages can arise. The interconnection of grounding systems via the armors of the MV cables, between secondary substations and HV/MV stations is herein analyzed to verify the effects on touch voltages in ground-fault conditions. In particular, two main issues are discussed: 1) the transfer of dangerous voltages to secondary substations, due to ground-faults occurring at the HV/MV station; 2) the reduction in the magnitude of the ground potential rise due to ground-fault conditions at secondary substations, thanks to the connection of their ground grids to the HV/MV station's grounding system.

M. L. DI Silvestre, L.D. (2018). Interconnections criteria of grounding grids in global grounding systems. In Conference Record - Industrial and Commercial Power Systems Technical Conference (pp. 1-8). Institute of Electrical and Electronics Engineers Inc. [10.1109/ICPS.2018.8369974].

Interconnections criteria of grounding grids in global grounding systems

M. L. DI Silvestre;L. Dusonchet;S. Favuzza;S. Mangione;L. Mineo;E. Riva Sanseverino;G. Zizzo
2018-01-01

Abstract

A Global Grounding System is defined as the combination of local grounding systems, obtained by their interconnection, which ensures, thanks to their proximity, that no dangerous touch voltages can arise. The interconnection of grounding systems via the armors of the MV cables, between secondary substations and HV/MV stations is herein analyzed to verify the effects on touch voltages in ground-fault conditions. In particular, two main issues are discussed: 1) the transfer of dangerous voltages to secondary substations, due to ground-faults occurring at the HV/MV station; 2) the reduction in the magnitude of the ground potential rise due to ground-fault conditions at secondary substations, thanks to the connection of their ground grids to the HV/MV station's grounding system.
2018
Settore ING-IND/33 - Sistemi Elettrici Per L'Energia
9781538610534
M. L. DI Silvestre, L.D. (2018). Interconnections criteria of grounding grids in global grounding systems. In Conference Record - Industrial and Commercial Power Systems Technical Conference (pp. 1-8). Institute of Electrical and Electronics Engineers Inc. [10.1109/ICPS.2018.8369974].
File in questo prodotto:
File Dimensione Formato  
08369974.pdf

Solo gestori archvio

Descrizione: Articolo pubblicato
Tipologia: Versione Editoriale
Dimensione 1.09 MB
Formato Adobe PDF
1.09 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/302898
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 3
  • ???jsp.display-item.citation.isi??? 0
social impact