This paper presents a method for the detection of series arc faults in electrical circuits, which has been developed starting from an experimental characterization of the arc fault phenomenon and an arcing current study in several test conditions. Starting from this, the authors have found that is it possible to suitably detect arc faults by means of a high-resolution low-frequency harmonic analysis of current signal, based on chirp zeta transform, and a proper set of indicators. The proposed method effectiveness is shown by means of experimental tests, which were carried in both arcing and nonarcing conditions and in the presence of different loads, chosen according to the UL 1699 standard requirements.

Artale, G., Cataliotti, A., Cosentino, V., Di Cara, D., Nuccio, S., Tine, G. (2017). Arc Fault Detection Method Based on CZT Low-Frequency Harmonic Current Analysis. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 66(5), 888-896 [10.1109/TIM.2016.2627248].

Arc Fault Detection Method Based on CZT Low-Frequency Harmonic Current Analysis

ARTALE, Giovanni;CATALIOTTI, Antonio;COSENTINO, Valentina
;
NUCCIO, Salvatore;
2017-01-01

Abstract

This paper presents a method for the detection of series arc faults in electrical circuits, which has been developed starting from an experimental characterization of the arc fault phenomenon and an arcing current study in several test conditions. Starting from this, the authors have found that is it possible to suitably detect arc faults by means of a high-resolution low-frequency harmonic analysis of current signal, based on chirp zeta transform, and a proper set of indicators. The proposed method effectiveness is shown by means of experimental tests, which were carried in both arcing and nonarcing conditions and in the presence of different loads, chosen according to the UL 1699 standard requirements.
2017
Settore ING-INF/07 - Misure Elettriche E Elettroniche
Artale, G., Cataliotti, A., Cosentino, V., Di Cara, D., Nuccio, S., Tine, G. (2017). Arc Fault Detection Method Based on CZT Low-Frequency Harmonic Current Analysis. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 66(5), 888-896 [10.1109/TIM.2016.2627248].
File in questo prodotto:
File Dimensione Formato  
TIM_2017_Arc Fault Detection Method.pdf

Solo gestori archvio

Descrizione: Articolo
Tipologia: Versione Editoriale
Dimensione 1.14 MB
Formato Adobe PDF
1.14 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/225940
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 125
  • ???jsp.display-item.citation.isi??? 92
social impact