Thermoeconomic diagnosis represents a promising technique for the detection of common faults in refrigeration systems, which are responsible of degradation in their energetic performance. Recently, the authors have carried out a sensitivity analysis of the performance of this method to the thermodynamic conditions of inlet air and to the geometry of the direct expansion coil, in case of degradation induced by evaporator fouling. The analysis showed that the method is able to detect this fault, but sometimes its quantitative assessments are not satisfactory. In order to understand more in-depth the origin of such results and identify margins for refinement of the technique, this paper is aimed at evaluating at what extent changes in the exergetic performance of faults-free components may negatively influence the model capability to detect the fouled evaporator and quantify the consequent additional exergy consumption. The results suggest that the method is particularly sensitive to the cost of “induced malfunctions” on the compressor and the condenser, especially when low coil depth or high relative humidity of inlet air are considered.

Piacentino, A., Catrini, P. (2017). On Thermoeconomic Diagnosis of a Fouled Direct Expansion Coil: Effects of Induced Malfunctions on Quantitative Performance of the Diagnostic Technique. JOURNAL OF SUSTAINABLE DEVELOPMENT OF ENERGY, WATER AND ENVIRONMENT SYSTEMS, 5(2), 177-190 [10.13044/j.sdewes.d5.0141].

On Thermoeconomic Diagnosis of a Fouled Direct Expansion Coil: Effects of Induced Malfunctions on Quantitative Performance of the Diagnostic Technique

PIACENTINO, Antonio;Catrini, Pietro
2017-01-01

Abstract

Thermoeconomic diagnosis represents a promising technique for the detection of common faults in refrigeration systems, which are responsible of degradation in their energetic performance. Recently, the authors have carried out a sensitivity analysis of the performance of this method to the thermodynamic conditions of inlet air and to the geometry of the direct expansion coil, in case of degradation induced by evaporator fouling. The analysis showed that the method is able to detect this fault, but sometimes its quantitative assessments are not satisfactory. In order to understand more in-depth the origin of such results and identify margins for refinement of the technique, this paper is aimed at evaluating at what extent changes in the exergetic performance of faults-free components may negatively influence the model capability to detect the fouled evaporator and quantify the consequent additional exergy consumption. The results suggest that the method is particularly sensitive to the cost of “induced malfunctions” on the compressor and the condenser, especially when low coil depth or high relative humidity of inlet air are considered.
2017
Settore ING-IND/10 - Fisica Tecnica Industriale
Piacentino, A., Catrini, P. (2017). On Thermoeconomic Diagnosis of a Fouled Direct Expansion Coil: Effects of Induced Malfunctions on Quantitative Performance of the Diagnostic Technique. JOURNAL OF SUSTAINABLE DEVELOPMENT OF ENERGY, WATER AND ENVIRONMENT SYSTEMS, 5(2), 177-190 [10.13044/j.sdewes.d5.0141].
File in questo prodotto:
File Dimensione Formato  
JSDEWES 2017 Piacentino - Catrini.pdf

accesso aperto

Descrizione: Full length manuscript
Dimensione 364.36 kB
Formato Adobe PDF
364.36 kB Adobe PDF Visualizza/Apri
On Thermoeconomic Diagnosis of a Fouled Direct Expansion Coil.pdf

Solo gestori archvio

Descrizione: versione editoriale
Tipologia: Versione Editoriale
Dimensione 376.76 kB
Formato Adobe PDF
376.76 kB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10447/223306
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 6
  • ???jsp.display-item.citation.isi??? 4
social impact